Engineering resources
Cable size reference and quick sizing helper
Quick references for site engineers and purchase teams. Values are indicative. Confirm final selections with manufacturer data and a qualified engineer.
Reference
Current-carrying capacity: 1.1 kV PVC, 3 / 3.5 / 4 core armoured
Indicative values compiled from widely published manufacturer tables based on IS 1554 (Part 1) / IS 3961 rating methods. Ground: laid direct at 30 °C ground temperature, soil thermal resistivity 1.5 K·m/W. Air: 40 °C ambient, single circuit, no grouping.
17 sizes
| Size (sq mm) | Copper | Aluminium | ||||
|---|---|---|---|---|---|---|
| Ground (A) | Air (A) | mV/A/m | Ground (A) | Air (A) | mV/A/m | |
| 1.5 | 18 | 15 | 25 | – | – | – |
| 2.5 | 24 | 21 | 15 | 19 | 16 | 25 |
| 4 | 32 | 27 | 9.5 | 25 | 21 | 15.5 |
| 6 | 40 | 35 | 6.4 | 31 | 27 | 10.4 |
| 10 | 54 | 45 | 3.8 | 42 | 35 | 6.2 |
| 16 | 69 | 60 | 2.4 | 54 | 47 | 3.9 |
| 25 | 90 | 82 | 1.5 | 70 | 64 | 2.5 |
| 35 | 110 | 100 | 1.1 | 86 | 78 | 1.8 |
| 50 | 132 | 123 | 0.81 | 103 | 96 | 1.35 |
| 70 | 163 | 152 | 0.57 | 127 | 119 | 0.93 |
| 95 | 197 | 187 | 0.42 | 154 | 146 | 0.68 |
| 120 | 224 | 216 | 0.35 | 175 | 169 | 0.55 |
| 150 | 251 | 246 | 0.29 | 196 | 192 | 0.45 |
| 185 | 284 | 282 | 0.24 | 222 | 220 | 0.37 |
| 240 | 326 | 333 | 0.21 | 255 | 260 | 0.3 |
| 300 | 365 | 378 | 0.19 | 285 | 295 | 0.26 |
| 400 | 410 | 435 | 0.17 | 320 | 340 | 0.22 |
Indicative only. Ratings vary by manufacturer, construction, installation method, grouping and ambient conditions. Always confirm with the manufacturer's data sheet and a qualified electrical engineer.
XLPE (IS 7098 Pt 1) cables of the same size typically carry around 20–30% more current. Use the manufacturer's XLPE table. Approximate three-phase voltage drop in mV per ampere per metre at conductor operating temperature. Single-phase drop is about 1.15 times the three-phase value. Apply derating factors for grouping, ambient temperature and depth of laying.
Calculator
Cable size helper
Enter the load and route length for a first-cut size from the table above, checked against your allowable voltage drop.
Load current
– A
- Size by current
- –
- Suggested (with voltage drop)
- –
Indicative only. Consult a qualified electrical engineer. This helper ignores derating for grouping and ambient temperature, motor starting current, short-circuit withstand and earth-fault loop impedance, all of which can require a larger cable.